Type "3 0 thhn" into a search box and you probably already know the shape of the job: a feeder, a service lateral, a panel upgrade, or a piece of equipment that needs a serious conductor. What you want now is confirmation. Amperage at the right temperature column, strand count, conduit size, and whether copper or aluminum is the smarter buy.
We have spent decades building cable for projects that range from metro lines to cement plants, and the questions buyers ask about 3/0 THHN are remarkably consistent. So here is the practical version, numbers first, sales pitch left outside.
Three-oh, 3/0, and 000 AWG all point to the same conductor size. At roughly 167,800 circular mils, or about 85 mm², 3/0 sits near the top of the everyday building-wire range: one size above 2/0 and one size below 4/0. It shows up when a 200 A feeder, a long service run, or a heavy equipment drop needs more metal than 2/0 can comfortably deliver.
THHN describes the insulation system rather than a separate product family. The letters stand for Thermoplastic, High Heat-resistant, Nylon-coated. In practice that means a PVC insulation covered by a thin nylon jacket, a 600 V rating, a 90°C dry-location temperature, and usually a dual THHN/THWN-2 marking that also allows 75°C wet locations. Standard constructions are gasoline and oil resistant, and most are sunlight resistant as well.
So the full description of what you are buying is: a 3/0 AWG conductor, copper or aluminum, insulated and jacketed to a 600 V building-wire standard, ready to be pulled through conduit or raceway.
Ampacity is where most ordering mistakes begin, because 3/0 THHN has three different numbers depending on which temperature column and which conductor material you are looking at.
| Conductor | 60°C | 75°C | 90°C |
|---|---|---|---|
| 3/0 copper THHN | 165 A | 200 A | 225 A |
| 3/0 aluminum THHN | 135 A | 155 A | 175 A |
Two habits keep you out of trouble. First, the conductor can run at 90°C, but the lugs, breakers, and equipment it lands on usually cannot, so the usable ampacity is normally taken from the 60°C or 75°C column unless the termination is marked otherwise. Second, the 90°C number is your starting point for correction factors: high ambient temperatures, more than three current-carrying conductors in a raceway, or both, all reduce the figure before you ever reach the panel.
Always check the values against the code edition your inspector enforces. Tables get renumbered and revised, and the authority having jurisdiction has the final word.
At this size, the conductor is almost always stranded, and the strand pattern affects how the cable behaves on a pull. A 3/0 Class B compressed copper conductor is commonly built from 19 strands, which gives a good balance of flexibility and diameter. Overall diameter for a typical 3/0 copper THHN lands around 0.6 to 0.63 in, roughly 16 mm, so plan your bending radius and pulling setup accordingly.
The PVC insulation does the dielectric work and the nylon jacket protects it during installation, which is why THHN resists abrasion so well in conduit. Because the jacket is thin, a nick during pulling can expose insulation, so inspection after the pull matters as much as the pull itself. Every reel we produce goes through the same conductor, insulation, and concentricity checks you can read about on our quality controls page.
PVC-Insulated Control Cable Family, 450/750 VPVC-insulated cable family rated 450/750 V, offered in screened, armoured, and flexible types for control, signaling, protection, and measurement installations.View Product →
For jobs that call for a PVC-insulated building wire in this size class, that product family is the direct equivalent of the construction described above.
The most common applications we ship this size for:
Just as important is where it does not belong. Standard THHN is not a direct-burial cable, it is not a tray cable unless specifically listed as one, and it should not be used in wet locations unless the product carries the THWN-2 or equivalent wet-location rating. For continuous flexing, portable cordage or a flexible cable is the correct choice.
A repeatable sequence saves hours of rework:
Voltage drop is where 3/0 usually earns its cost. A 200 A load on a 150 ft run of 3/0 copper at 240 V loses only around 4 to 5 V, under 2 percent, which is why this size appears so often on longer service runs where 2/0 would have strained the limit.
Conduit sizing deserves the same attention. Three 3/0 conductors need a noticeably larger raceway than a typical branch circuit, and the fill tables, not a rule of thumb, should decide the number. Bending radius, pull length, and lubricant choice all matter more at this diameter than they do at 12 AWG.
Before you commit, it helps to see the alternatives side by side:
Heat-Resistant Cross-Linked Polyolefin Insulated CableCross-linked polyolefin insulated cable rated 450/750 V, available in 105°C, 125°C, and 150°C low-smoke halogen-free flame-retardant types for fixed installations.View Product →
If the route passes through wet or humid areas, the cross-linked polyethylene option above is usually the more comfortable long-term answer.
A short checklist before you approve a purchase order:
If you would like to know who is behind the cable before you specify it, our company background covers the factory, the certificates, and the way we work with project teams.
Not automatically. THWN is the wet-location version, and many modern cables carry both markings on the same jacket. Check the print legend rather than assuming.
Copper 3/0 THHN is typically 200 A at 75°C and 225 A at 90°C; aluminum is typically 155 A and 175 A. Terminations and derating usually decide the real number.
Only in a raceway and only when the cable carries a wet-location rating. Direct burial calls for a cable designed for it, such as a USE type.
Size, temperature column, material, and installation environment decide almost everything about a 3/0 THHN order. Get those four right and the rest is logistics: reel length, delivery date, and whether the conductor arrives with the jacket printing your inspector expects to see.
If a run is borderline between two sizes, run the voltage drop calculation before you round up. It is cheaper to spend ten minutes with a calculator than to pull a conductor that will not pass inspection.