The product is manufactured according to the standards of GB12706 and GB12666, or IEC, BS, DIN, ICEA, and JIS upon request.
The product is suitable for use in power distribution lines or fixed installations with rated power-frequency voltage up to and including 0.6/1 kV.
Operating characteristics
Rated power-frequency voltage Uo/U:0.6/1 kV.
Max.permissible continuous operating temperature of conductor(PVC/XLPE):70℃/90℃
Max. short-circuit temperature of the conductor shall not exceed(5s maximum duration).
PVC: cross-section of conductor≤300mm2-160℃
Cross-section of conductor>300mm2-140℃
XLPE:250℃
The ambient temperature under installation should not be below 0℃.
The bending radius of a single-core cable should be than 20 times the cable diameter.
The bending radius of multicore cable should be than 15 times the cable diameter.